Home › CVE › Cloud & containers
CVE-2023-25915 — Danfoss AK-SM 800A Series Improper Input Validation Vulnerability
Research article
Danfoss AK-SM 800A Series Improper Input Validation Flaw (CVE-2023-25915) Allows Remote Command Execution
| CVE | CVE-2023-25915 |
|---|---|
| Vendor and product | Danfoss AK-SM 800A Series |
| Published | November 25, 2026 20:20 UTC |
| Research cut-off | November 25, 2026 20:15 UTC |
| Sources reviewed | 2: NVD record (last modified 2026-06-17); CISA KEV catalog |
Executive summary
CVE-2023-25915 is an improper input validation weakness (CWE-20) in the Danfoss AK-SM 800A Series, which the record and CISA summary say could let a remote attacker run arbitrary commands on the affected system [1, 2]. NIST NVD scores it CVSS 3.1 8.8 (High) with vector CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H [1]. The vendor lists affected versions as below 3.3 in the CVE record, while NVD's configuration lists 3.3 or earlier, a discrepancy that must be resolved before any version is treated as safe [1]. The vector indicates network reachability, low privileges and no user interaction are required, although the sources do not describe the specific interface or configuration [1]. CISA lists the CVE in its Known Exploited Vulnerabilities catalog with evidence of exploitation in the wild, added 2026-11-25 with a federal due date of 2026-11-28; ransomware use is recorded as Unknown [2]. The most important immediate action is to inventory every AK-SM 800A device, record its firmware version, remove any direct network exposure, and obtain the vendor advisory DSA-2023-08-01 for the mitigation and fixed-version instructions [1, 2].
Key points
- CVE-2023-25915 is an improper input validation flaw (CWE-20) in the Danfoss AK-SM 800A Series, scored CVSS 3.1 8.8 High [1].
- The reported outcome is remote arbitrary command execution on the affected system [2].
- CISA lists the CVE in KEV with evidence of exploitation in the wild; added 2026-11-25, federal due date 2026-11-28 [2].
- The vendor range below 3.3 conflicts with NVD's 3.3-or-earlier configuration; the fixed version must be confirmed in advisory DSA-2023-08-01 [1, 2].
- Immediate action: inventory all AK-SM 800A devices, remove untrusted network exposure and apply the vendor's mitigations [1, 2].
Vulnerability identification
| Field | Value |
|---|---|
| CVE ID | CVE-2023-25915 [1] |
| Vendor | Danfoss [1, 2] |
| Product | AK-SM 800A Series; NVD's configuration names the AK-SM 800A firmware [1, 2] |
| Component | Not identified in the reviewed sources |
| Record status | Analyzed [1] |
| Published | 2023-08-21T21:15:09 [1] |
| Last modified | 2026-06-17T05:42:15 [1] |
| CWE | CWE-20, Improper Input Validation [1] |
| CVSS 3.1 base score | 8.8, High; vector CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; scored by NIST NVD (Primary) [1] |
| Other CVSS scores | None in the pack [1] |
| Related identifiers | Third-party advisories DIVD-2023-00025 and the DIVD CVE page listed in the record [1]; vendor advisory DSA-2023-08-01 [2] |
| CISA KEV status | Listed; date added 2026-11-25; federal due date 2026-11-28 [2] |
CWE-20 describes software that does not validate input, or validates it incorrectly, so that data outside the expected form can change how the software processes it [1]. Here the weakness is classified only at the CWE level; the record does not state which input or function is involved.
Vulnerability description
The record and the CISA entry both state that the flaw is an input validation failure in the AK-SM 800A Series that could let a remote attacker run arbitrary commands on the affected system [1, 2]. The CVSS vector scores confidentiality, integrity and availability impact as High, with scope unchanged [1]. Under the vector, exploitation needs network access and low privileges, and no user must take action [1]. The sources do not establish the specific input, interface or code path involved, so the mechanism cannot be described beyond the input validation classification.
Attack surface and exploitation prerequisites
| Prerequisite | Status | Source |
|---|---|---|
| Network access | Required per AV:N in the vector; the reachable port or service is not identified | [1] |
| Adjacent or local access | Not required per the vector | [1] |
| Authentication and privilege | Low privileges required per PR:L; the privilege level and account type are not described | [1] |
| User interaction | None required per UI:N | [1] |
| Required configuration or feature | Not established by the pack | [1, 2] |
| Remote reachability in practice | Stated as remote attacker in CISA's summary; internet exposure of deployed units is not established | [2] |
The prerequisites above come from the CVSS vector and, for remote reachability, from the CISA summary. They are not confirmed by a vendor analysis or a technical report in the pack.
Impact analysis
| Security property | Technically indicated impact | Source |
|---|---|---|
| Confidentiality | High per C:H in the vector | [1] |
| Integrity | High per I:H; command execution is the reported outcome | [1, 2] |
| Availability | High per A:H | [1] |
| Authentication and authorization | Low privileges are required, so the flaw is reported to lift access beyond those privileges; the exact boundary crossed is not described | [1, 2] |
| Business operations and data | Not described in the reviewed sources | None |
| Regulatory obligations | US federal agencies must meet the CISA due date and the BOD 26-04 guidance cited in the KEV entry [2] | [2] |
The reported outcome is command execution on the device. Consequences for industrial or building control processes connected to these controllers are plausible downstream effects, not documented impacts in the pack.
Affected products and versions
| Vendor | Product | Affected versions | Fixed version | Source and qualification |
|---|---|---|---|---|
| Danfoss | AK-SM 800A | Below 3.3, as published by the vendor in the CVE record [1] | Not stated explicitly in the pack | [1]; vendor advisory DSA-2023-08-01 is named in [2] but its content is not in the pack |
| Danfoss | AK-SM 800A firmware (NVD configuration) | 3.3 or earlier, as NVD analysed the configuration [1] | Not stated | [1]; conflicts with the vendor range, so 3.3 may or may not be affected |
The vendor range and the NVD configuration differ at the 3.3 boundary [1]. The pack does not provide a complete range, hardware variants, deployment types or configuration-specific exclusions.
Exploitation and threat intelligence status
- Confirmed exploitation in the wild: CISA states it has evidence of exploitation in the wild and lists the CVE in KEV, added 2026-11-25, due 2026-11-28 for US federal agencies [2].
- Ransomware use: recorded by CISA as Unknown [2].
- Public proof-of-concept: no public exploit reference appears in the pack.
- Threat actors, campaigns and targeted sectors: not attributed in the pack.
- The KEV entry is recent relative to the NVD record, which was last modified on 2026-06-17 [1, 2]. The absence of public evidence in the pack does not show that exploitation has not occurred.
Detection and exposure assessment
The pack gives no product-specific detection query, log source, event ID or telemetry pattern for this CVE, so the steps below are limited to inventory and version comparison.
- Build an inventory of every AK-SM 800A Series device, including its network location and whether it is reachable from outside the local control network [1, 2].
- Record each device's firmware version using the device's own management interface or asset records; the pack does not name the command or screen that reports it.
- Flag any device below 3.3 as affected under the vendor range [1]. Flag devices at exactly 3.3 for review, because NVD's configuration includes that version [1].
- A version match is not proof of exploitation, and a version outside the affected range is not proof of safety, since the pack lacks indicators and the vendor fixed-version statement [1, 2].
Remediation
Immediate mitigation:
- Obtain the vendor advisory DSA-2023-08-01 and follow its mitigation instructions, as CISA directs [2]. The advisory content is not in the pack, so the specific measures are unknown.
- Remove any direct internet or untrusted-network path to AK-SM 800A devices, and restrict access to them with firewall rules to the management systems that need it. This follows from the network attack vector in the CVSS vector [1]; the pack does not name the ports or services to block.
- If mitigations are unavailable, the CISA required action is to discontinue use of the product [2].
Permanent fix:
- Update the affected devices to the fixed release that the vendor specifies in DSA-2023-08-01. The vendor range implies 3.3 as the first unaffected version, but NVD's configuration includes 3.3, so the vendor's confirmed fixed version must be used [1, 2].
- After the update, confirm the firmware version on each device reads the fixed version from the vendor advisory, and re-run the inventory in the detection section.
- Confirm the upgrade procedure, prerequisites, backup requirements and whether a restart is needed from the vendor advisory; none is in the pack.
Remediation checklist
- Inventory every Danfoss AK-SM 800A Series device, including its network location and whether it is reachable from outside the local control network [1, 2].
- Record each device's firmware version from its management interface or asset records, and flag any below 3.3 as affected under the vendor range [1].
- Review every device at firmware 3.3 as well, because NVD's configuration includes that version and conflicts with the vendor range [1].
- Obtain Danfoss advisory DSA-2023-08-01 and apply its mitigation instructions to each device before the permanent fix is available [2].
- Remove any direct internet or untrusted-network path to AK-SM 800A devices and restrict management access with firewall rules; verify by testing reachability from outside the control network after the rule change [1, 2].
- If mitigations are unavailable, discontinue use of the affected devices or isolate them, as CISA's required action directs; US federal agencies must complete this by 2026-11-28 [2].
- Update each device to the fixed firmware named in DSA-2023-08-01, then confirm the installed version on every device matches it [1, 2].
- Before any update or change, back up each device's configuration and record its current firmware version, so the change can be verified and rolled back if needed [2].
- If exploitation is suspected on a device, preserve its logs and configuration before remediation, following the forensics triage guidance CISA references [2].
- Re-run the inventory and version check after remediation and record the results, so the exposure status is documented [1, 2].
Evidence gaps
- Not established by the reviewed sources: the affected component, function and input that trigger the CWE-20 flaw, which is needed to explain the root cause and test whether controls block it; the vendor advisory DSA-2023-08-01 would be the first source to check.
- Not established by the reviewed sources: an explicit fixed version. The vendor range below 3.3 conflicts with NVD's 3.3-or-earlier configuration; the vendor advisory or a corrected CVE record would settle it.
- Not established by the reviewed sources: the vendor's mitigation steps, because the advisory content is not in the pack; DSA-2023-08-01 is named in the CISA entry and would provide them.
- Not established by the reviewed sources: the network ports, services, interfaces or configuration features that expose the vulnerable function; the vendor advisory or a technical analysis would be needed.
- Not established by the reviewed sources: exploitation details, public proof-of-concept references, threat actors or targeted sectors; CISA's known-exploitation evidence and any vendor incident reporting would be needed.
- Not established by the reviewed sources: indicators of compromise, log sources, event IDs or telemetry patterns for this CVE; the vendor advisory, CISA guidance or a forensic report would be needed.
- Not established by the reviewed sources: the device models, hardware variants and deployment types affected, and any configuration-specific exclusions.
- Not established by the reviewed sources: the content of the third-party DIVD advisories DIVD-2023-00025 and the DIVD CVE page listed in the NVD record, which may provide technical detail.
- Not established by the reviewed sources: ransomware use; CISA records it as Unknown, so the status is unresolved.
- Not established by the reviewed sources: any CVSS score other than the NVD CVSS 3.1 score, and any second scorer's view of the severity.
References
- CVE-2023-25915 record. NIST National Vulnerability Database (NVD), 2026-06-17. https://nvd.nist.gov/vuln/detail/CVE-2023-25915. Accessed 2026-11-25.
- Known Exploited Vulnerabilities Catalog: CVE-2023-25915. Cybersecurity and Infrastructure Security Agency (CISA), 2026-11-25. https://www.cisa.gov/known-exploited-vulnerabilities-catalog. Accessed 2026-11-25.
Summary
Danfoss AK-SM 800A Series contains an improper input validation vulnerability that could allow a remote attacker to run arbitrary commands on the affected system. Required action: Apply mitigations in accordance with vendor instructions, ensuring compliance with CISA’s BOD 26-04 Prioritizing Security Updates Based on Risk (see URL in Notes) guidance and CISA’s “Forensics Triage Requirements” (see URL in Notes). Follow applicable BOD 26-04 guidance for cloud services or discontinue use of the product if mitigations are unavailable. Stakeholders are responsible for evaluating each asset's internet exposure and ensuring adherence to BOD 26-04 patching guidelines. (Federal remediation due 2026-11-28)
Severity breakdown
High · 8.8
An attacker with a normal user account can exploit this over the network, without any user action.
- Attack from
- the network (remotely)
- Attack complexity
- low (no special conditions)
- Login needed
- yes, a normal user account
- User action needed
- no
- Scope
- stays within the vulnerable component
- Impact
- high on confidentiality, integrity and availability
Weakness
- CWE-20: Improper Input Validation
Affected and fixed versions
| Product | Affected versions | Fixed in |
|---|---|---|
| Danfoss AK-SM800A | < 3.3 | — |
CISA KEV
Exploited in the wild
- Listed as
- Danfoss AK-SM 800A Series Improper Input Validation Vulnerability
- Added to the catalog
- November 25, 2026
- Federal due date
- November 28, 2026
- Ransomware use
- Not known
- Forensic triage
- Required by CISA: look for signs of compromise, not just the patch
References by type
Vendor advisories
Other references
Affected
- Danfoss AK-SM 800A Series
Frequently asked questions
What is CVE-2023-25915?
CVE-2023-25915 is an improper input validation weakness (CWE-20) in the Danfoss AK-SM 800A Series, which the record and CISA summary say could let a remote attacker run arbitrary commands on the affected system. NIST NVD scores it CVSS 3.1 8.8 (High) with vector CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H. Weakness type: Improper Input Validation (CWE-20).
How severe is CVE-2023-25915?
CVE-2023-25915 has a CVSS 3.1 base score of 8.8 (high), from NVD. An attacker with a normal user account can exploit this over the network, without any user action.
Is CVE-2023-25915 being exploited?
Yes. CISA lists CVE-2023-25915 in its Known Exploited Vulnerabilities (KEV) catalog, added November 25, 2026: it has been exploited in real attacks. US federal agencies must fix it by November 28, 2026.
Which versions are affected by CVE-2023-25915?
Danfoss AK-SM800A < 3.3.
How do I fix CVE-2023-25915?
Inventory every Danfoss AK-SM 800A Series device, including its network location and whether it is reachable from outside the local control network. Record each device's firmware version from its management interface or asset records, and flag any below 3.3 as affected under the vendor range. Review every device at firmware 3.3 as well, because NVD's configuration includes that version and conflicts with the vendor range.
Timeline & sources
- CISA KEV: CVE-2023-25915 — Danfoss AK-SM 800A Series Improper Input Validation Vulnerability
- CISA advisories: CISA Adds 10 Known Exploited Vulnerabilities to Catalog
References
- NVD — CVE-2023-25915
- CVE.org record
- CISA Known Exploited Vulnerabilities catalog
- GitHub Advisory Database
Related vulnerabilities & news
- Mitel MiCollab Unrestricted File Upload Vulnerability (CVE-2026-133275)
- Mitel MiCollab Authentication Bypass Vulnerability (CVE-2026-133324)
- Danfoss AK-SM 800A Series path traversal (CVE-2023-25914) exposes file reads via XML interface
- Mitel MiCollab AWV Unauthenticated OS Command Injection in CVE-2026-133323 (CVSS 3.1 10.0)
- CVE-2026-133303 — Mitel MiCollab XML Injection Vulnerability